Modbus RTU Analog Input 4 Channels
• Support 4 Analog Inputs
• 3 Models to cover various applications
AI-140-16 : 4~20mA x2 + 0~10V x2 channels
AI-140-16A : 4~20mA x4 channels
AI-140-16V : 0~10V x 4 channels
• Support Analog Devices to Modbus RTU
• Support 4 Analog Inputs
• 16 bits Resolution
• 3 Models to cover various applications
AI-140-16 : 4~20mA x 2 Channels + 0~10V x 2 Channels
AI-140-16A : 4~20mA x 4 Channels
AI-140-16V : 0~10V x 4 Channels
System
• RAM : 64KB Internal SRAM
• ROM : 256K bytes Flash ROM
• Watchdog : Built in H/W Watchdog timer
Serial Port
• Port : RS-485 x 1 Port (2-pin Terminal Block)
• Speed : 300 bps ~ 115.2 Kbps
• Parity : None
• Data Bit : 8
• Stop Bit : 1
• RS-485 : Data+ , Data-
• Built–in : RS-485 pull high / low Terminal Resistor
• Protection : 485 Surge Protection
• Built in 15KV ESD protection for all signals
Power
• Power Input support DC Jack and Terminal Block
LED
Analog Input
• Resolution : 16 bits
• Input numbers : 4 channels.
• Input Impedance:
Voltage: 1.33M Ohm
Current: 120 Ohm
• Channels: to be assigned on order.
4~20mA x2 + 0~10V x2
or 4~20mA x4 Channels
or 0~10V x 4 Channels
• Accuracy: mA +-0.5%, V +- 1%.
Regulatory Approval
• FCC Part15 Class A
• CE EN55022 Class A, EN55024
• RoHS Compliance
Warranty
Warranty period : 1 year.
Environment
Storage: -10°C ~ 85°C (-14°F ~ 185°F)
• Humidity : Operating: 10% ~ 95% non-condensing
Storage: 5% ~ 95% non-condensing
• Dimension: 110 * 90 * 26 mm ( W * D * H )
• Weight : 95 gm
Software features
• Modbus: Convert Analog signal to Modbus protocol
• Support Modbus RTU Slave
• OS Supported : Win 2000/2003/XP/Vista/Win 7/Win 8
• Configuration : Window Utility
Product Image:
click above photo to get large view.
Data Sheet:
AI-140-16-Modbus_DataSheet_201910a.pdf
User's Manual:
AI-140-16-Modbus_UserManual_202001a.pdf
modbus-rtu-protocol-for-4ai-hiresolution_4ch.pdf
Drivers: